Here are the specifications of three models of Homage Inverters, Vision 500, Vision 1000 and Vision 2000, and common problems with solutions.
Admin’s Note: Although, this post is about an old Homage inverter series, you can still ask questions related to all new & discontinued Homage Inverters in comments section below.
I have tried to explain several error codes / faults in comments section. So instead of posting abusive comments, spend time reading through comments. Note that inverter error codes are not standardized. Each code could have different details for different model. So my explanation could be wrong too. Better take your power inverter to service center if it keeps giving same error over and over again.
After receiving thousands of complaints about Homage inverters, I shall recommend to avoid these inverters. Instead go for CyberPower Inverters. Their build quality is good and their simulated sine wave current is safe for devices. Your fan capacitors, fan regulators, energy savers, PC power supply and other electronic devices will not burn randomly. I am recommending these based on my personal 7+ years experience with CyberPower Inverters.
CyberPower Inverters: Review & Description
Specifications:
Problems & Solutions:
- For more details, read this topic: UPS Problems And Possible Remedies
Solution for some other problems related to Homage Power Inverters:
1- UPS is running continuously in inverter mode despite of main electricity presence.
Sol: Make sure that input plug is connected and providing electricity to the UPS. Sometimes, fuses of input melt resulting in no input. You need to change the fuses. If you can not do it yourself, take it to the service centre. It also happens that if input voltage is too low to be acceptable, UPS does not switch over to main electricity supply. Check to make sure that that is not the case. If that is true, choose wide range from UPS for input. Note that choosing wide range increases the switch over time of UPS. You may also install a stabilizer to fix the voltage issue.
2- Batteries are connected properly but not getting charged. Electricity is also available.
Sol: Check to make sure that battery terminals are rust free. If they are rusty, electricity won’t flow through them. Clean them or change them if they are rotted due to corrosion. If rectifiers or step down transformer of charger are burnt, batteries will not be charged. You need to get your UPS repaired. Usually, it happens only if cooling fan of UPS was not working properly or UPS is placed at extremely hot place. Quality of internal circuitry also matters.
3- Batteries are charged but UPS is not providing any backup. In fact, UPS is not switching to backup mode.
Sol: Usually it happens if battery terminals are corroded. UPS can not draw enough current through them to provide the backup. You need to clean or change the battery terminals. Also check to make sure that output of UPS is properly connected. If everything looks fine from the outside, then problem could be inside of power inverter.
4- Everything seems fine but UPS is still not working. Batteries and wiring are also okay.
Sol: In that case, UPS might be faulty. You need to take it to the service centre. Note that, if UPS is filled with dust, that might also be responsible for the problem. If fan of UPS is stuck due to the mud inside it, UPS will not work either. Clean your UPS with a wind blower.
Also Read:
Functions of Different Power Inverter/UPS Buttons, Switches
Juan
Hi, we sell your Tron 800w/1600w inverters.
We are experiencing a difficulty with an Error “3′ how do we fix this?
Mohsin
I have recently purchased Homage OCTA DUO HOD 1212 1000W – but its not providing backup enough from battery. Whereas I have purchased 185Amp Tall Tubbler Phoenix new battery as well.
When my Homeage inverter shows low battery alarm – i connect the same battery at the same time on another Inverter (NS Inverter) it shows 2xbar of battery & provide backup of more than 30minutes.
Please guide me what is the issue.
Ashfaq
Sir I bought homage inverter and facing A91 error and alarm is buzzing ever second
Ali
i have Homage OCTA Duo HOD -1212SCC Inverter
So now there is buzzer for PV charger ntc disconnected .
Should i call to the electrician or technician or do some thing easy myself to solve the problem,
Muneer Ahmed
My inverter problem is error 4 please give me some solution
Fakhar Zaman
Hey Sir, my homeage UPS giving msg of error 6, how much cost will be to repair ??
Plz give response ASAP
Gohar
I have homage inverter HEx-3011scc
Which is working properly but only on AC voltage
Please guide me how to install solar panels with it also please tell how many solar panels and how much watts and how to connect them, thanks in advance
Abu bakar
Hi Sir I’ve Homeage Octa Duo 1212SCC. It is showing Fault A91 and in instructions manual it is written that A91 mean PV CHARGER NTC DISCONECT while we are not using solar pannel. Please Guide me about this.
Muhammad Shafique
Sir I am facing the problem that it’s buzzing every second showing fault PV charger NTC disconnected how can I solve it please you can tell me in detail
Ali
did you get the answer if yes tell me i have same problem too.
Mian Javed
I have Installed Homage Inverter Neon 2003 (24 Volts 1500 Watts ) working excellent Cooling fan stopped after completion of charge but last some days fan not stop when charging complete charging light also stop but fan continuously running in full speed. Two nos. “Millat M-135” batteries are connected in serious circuit since last 18 months and backup well up till now. please guide that how to resolve the said issue?
Talal A.
It could be an internal fault in Inverter. May be take it to service center to get it fixed.
Mian Javed
Deer
I have homage neon ups 2003 24 volts 1500 watts
Talal sb. Ups working perfect but last 15 days about the cooling fan not stoping , charging stop when battery fully charged . Battery backup, and other all function are in working very well . Only ups fan running 24 hours (2 Nos. Millat batteries connected since last 18 months)
Pl. Guide who can resolve this issue
Adul
I have hex 1004 homage inverter working excellent but inverter fan not stop when charging complete plz confirm what is the issue and how to resolve it?
Fahad
Ups is not working on Wide range when voltages come to 169 ups goes to backup mode charging mode stopped
Talal A.
Are you sure its 169 because abrupt voltage drop and recovery may not be displayed by the LCD properly.
Aamir
My homage ups stop working and shows fault 4 on lcd
Amir
My Homeage Tron duo 1211sc model, while connecting with Solar, shows only one lower bar.even though battery has full charge but slowly charge of battery goes discharge but utility is also not charging at time resultantly ups shutdown upon loadshedding. However working perfect when solar not connected. Kindly help. Regards.
Mian yousaf
Aoa sir i have installed homage tron due with four 170w solar plates in parralel.the problem is that when i set on the power button it only run the appliances like fan or lights it does not charge the battery at same time even if i putt off all the appliances..but when i do off the power button then it charge the battery but now it does not ON the appliance..sir plz help me what can i do.is it fault of setting or hardware of 1000w homage ups.tron due
Ozair
Aoa Talat and Anyone who can help me
My Ups is charging fine, terminals are clean, battery is AGS 105AH 7 months old. No faults been displayed. But as soon as the power goes, it turns off after a backup of 30 to 45 mins, with hardly one Fan working only. No beeps, no warning, nothing, it just turns off.
There’s been power fault today so it hasn’t charged for more than 1 and half hour in one go. So as soon as power goes, it switches off. I press the power button and hold it, it turns on. Now the charge is sufficient to keep it going for at least 30 mins, but as soon as i let the power button go, ups turns off. I have put some weight on it in order to keep supplying the power and its going fine. Is it the power button’s fault??
I have homage hexa 1204
Kindly guide me. Thank you
aftab ahmad
universal model HTD 1011scc main low charging ke seting kesy ke jati hy ?
wali
fault 9 error and its solution plz
Zubair Raja
sir i have homage 1212 duo ups 2019. and installed with HAWK tubeler battery 230 amp. is this battery charge well with this ups or i need some extra setting in ups?
pls help me.
Aurangzaib
my homeage inverter giving error 09 on screen. no output/backup
Fawad Ahmad
cooling fan is continuously remain ON in every mode of operation even after charging batteries.
Muhammad Khurram Khurshid
My inverter is doing the same, and i checked the current going to batterty is about 6amp to 8amp and also batter is very hot, i disconnect the battery then after 5 seconds fans turned off, i take it to 2 different technicians, they says your UPS is fine, I am not satisfied by their statement, UPS was not behaving like this about 3 4 weeks ,
any suggestions ???
Mohammad
Same problem with my Hyundai hybrid inverter if you find any solution plz let me know
03459079992
Kashif
Hi ,
i recently installed homage tron duo. HTD 1211 inverter. it had no problem since i used it for 3 months . but recently i had to disconnect all the installation for better wiring and place, when i reconnected the battery , accidentally it was connected inverter’s Positive connector to battery’s negative , and inverter’s Negative connector to battery’s positive . more over inverter’s power’s button was at On position. there was a spark but after that Inverter is no longer able to power on or do any thing active.
will it cover under warrenty ? or what will be solution now.?
Talal A.
It’s not covered under warranty. you would have to pay for repair. The stupid thing about Homage inverters is these don’t have reverse polarity protection feature. As usual crap product from crap assemblers aka R&I.
Tanveer Ahmed
My homage tron duo 800 watts.Atfer one day installation it starts beeping and when i made it off it stops.plz solution
Talal A.
If installation was correct than there might be some manufacturing defect in it. Claim your warranty.
Tanveer Ahmed
Dear my ups is beeping continuously but when i pushed the button off then it stops today is the second day of installation.plz
Mohammad Farooq
Homage Inverter (HTD-1211SCC) I have purchased but cooling fan is continuously remain ON in every mode of operation even after charging batteries.
ahamad
ups homage 100i not providing 220 v at out put pls help me for trace problem
m ishtiaq
AOA. sir merra Homage ups 3,4 din bad red light show krta hai or alarm bolta h. phir of kr k on krta hon to theak chalta h.
kiya problem h ups me???
Muhammad Sheraz
replace ups fan
Shahid Khan
Aslam o Alaikum, I have installed Homage 1011SCC since 4 days ago. My UPS does not tripp after charge the battery full and DC fan of UPS also running since 4 days. Moreover, 1 cell on battery fall in just 15 Seconds but it will charge in 10 Minutes approximately. Reply me as soon. Thanks
Waseem
I have installed homage axiom 3002 with solar.i used it just as a invertor. when solar controller voltage 24.8 v goes on ,my homage axiom 3002 given beep and shut down all load. How i increase axiom 3002 increase battery voltage
Abbas
sir HTD 2211 model main fault 16 and beeps
Ali
AoA sir today I received error code 13 on home age tron duo 1011 solar voltage 19 volt but not switch to solar after few minutes beep on error code 13, shift on solar line, usually it done on morning time please tell me why
Talal A.
Did you try after shutting it down and restarting? If problem persists you should claim its warranty or get it repaired.
wasim
dear sir. i have installed homage hybrid ups tron 800.not using solar point. on ac is working.
today i found a problem that green ligt of charing battry is continiously blinking. why it is so?.
while it is blinking since 20 hrs. why it is so. i think there is problem. plz guide
Talal A.
How old are you batteries?
Charger of your inverter is failing to cut off charging. In most cases battery is the culprit.
FAYYAZ AHMED
FAULT CODE 13
AND FAULT CODE 16
PLZ BRIEF REGARDING CAUTION AND BEEP
Kamran
AOA, Sir i have homage hexa 1004 UPS. when i want to switch off ups from switch off button it doesn’t work. Switch off button problem??????
Talal A.
you need to switch off its input as well. you might be switching off its backup mode only
Ali
AoA, I installed 450 watt solar system with homeage tron duo 1011 ups, battery charging setting set only solar but solar charger current only 2 amp on 12 volt, not increased while at at that time solar output current upto 20 amp, how can I increase battery charging current?
Regard
Ali
Talal A.
Power Inverter automatically adjusts charging current for batteries. It’s for the safety of battery.
Ali
Thanks for your reply, please tell me also why invertor run on backup mode whole day while solar output is enough for output load, not shifted to line 2,
Talal A.
Please check the settings.
masood
i want to use utility once solar energy decrease instead of use of batteries, how it possible in HTD-2011SCC, can i change the battery voltage back to utility, in this setting what happen in case of UPS mode, i mean no utility and no solar
Talal A.
See this video to setup inverter to use utility when solar power goes down.
Raheel Karachi
Hi there. My UPS is beeping continuously with an interval of one second. Last week it happened I switched it off for about 5 minutes then it stopped. Please let me know why this is happening?.
Shoaib
Need homeage solar inverter setting catalog
Raheel Karachi
It is not Solar
Raheel Karachi
It is TRON Duo
Eric
Hi, I just bought Homage Tron 1011 with 800 W capacity and attached Pheonix UGLT 200 battery. The problem is that my UPS never goes to rest mode and its cooling fan remains on all the time without break. Is there a prob??
Nizwa
I am using homeage matrix 1000. I recently bought a new battery. It worked fine for a few days but now, somehow whenever the main supply is cut off, the ups fails to provide back up after few minutes. it seems that the ups is not charging the battery.
although it shows fully charged on the lcd display.
Could there be a problem with the ups or the battery?
Ki
How to turn off homage ups without unplugging it?
Talal A.
Turn off UPS from power socket on the wall. Then press power button on UPS to shutdown its backup mode.
Maha
Hi. My ups works for 2 hrs only and after that it gets off. Battery and ups are new (dry battery, homage UPS ). Is it that the battery time is set to 2hrs ?? How can we change the setting ?
Talal A.
How many fans, lights and other appliances are you running on this UPS?
Tahir
Salaam. Suddenly current wires are connected with ups wire and after then red light on and ups rings the bell plz suggest what should I do
Talal A.
Did you reverse the polarity?
Nasar
Salam sir mn ne osaka tublar battery plate deep cycle battery homge axiom 1002 k sath lgai ha ab use 15A pe ya 20A mn se kis pe rkhna ha or wide or narrow ka b bta dn
Shahbaz
Kindly define homage HTU- support battery in ampere
Mehmood
sir my homage tron duo ups is not showing voltage when charging on solar is there something wrong?
Asad - Ullah
Hello Sir,
I have homage tron uno. Before few days it was working good with 4 to 5 hours backup. But from last two months it’s creating problem. Showing the battery is full charged but backup is only 10 minutes.
I have also taken the battery to concern. it is OK. connectors are also cleaned. But still same problem. Please advice
Talal A.
Connect different battery and check your inverter.
Muhammad Ashraf Bhatti
please describe in detail the push button setting of homage trons duo 1000 Watt for solar ?
Shamrez
sir my ups 1211 is not giving out put power and also have error 3 coming please suggests what can i do.
i reset and change the battery also but same issue .